Dirk Witthaut and researchers identify synchronized battery self-tests as the cause of global power grid frequency drops
Researchers led by Dirk Witthaut have identified that synchronized self-tests in battery-based uninterruptible power supplies (UPS) and stationary batteries are causing a recurring frequency drop in power grids across five continents. For years, grid operators observed a small frequency dip every 60 seconds that appeared to be a coherent signal rather than random noise. By installing over 80 smart power quality meters on the Jülich campus, the team confirmed that these internet-connected devices check their state of charge simultaneously because their clocks are synchronized via the network time protocol. While a single check is imperceptible, the collective action of millions of devices creates a measurable disturbance. In Ireland, where data centers represent a significant portion of the grid load, the minute-by-minute frequency drop quadrupled between 2016 and 2021. To mitigate the issue, the researchers recommend that manufacturers add randomization to the charge-check schedules. One manufacturer has already released a software update to eliminate strict periodicity, though the devices still perform the self-tests at fixed times.